In the example, the following was set for tunnel section 2: ● Manual operation for the fan |
By double-clicking on a symbol for a lamp, you access the automatic / manual operating mode for the lighting in the corresponding tunnel section. |
Low speed (slow) ● Clockwise |
In the example, for the left interior light was set in tunnel section 2: ● Manual mode |
The fan blows at slow speed in clockwise direction.For maintenance tasks, it may be advisable to manually set the brightness in the tunne | Night light The lamp emits subdued light.By specifying the sensor values, you can test the function of the tunnel application |
By
double-clicking on a box for the sensors, you access the automatic / manual operating mode.
In the example, the following was set for tunnel section 1:
● Manual operation for setting the CO limit value (air quality sensor)
● CO limit value of 28
● Manual operation for specifying the limit value for the vision (turbidity sensor)
● Value for the vision of 2You have configured and programmed the tunnel application. The following sections
describe how to commission the tunnel application.
Further information on commissioning is available in the system manual of Redundant
System R/The CPUs only support pre-formatted SIMATIC memory cards. If required, format the
SIMATIC memory cards before using them in the CPU.
Procedure: Insert a SIMATIC memory card into the left-hand CPU as follows.
1. Open the front cover of the CPU.
2. Ensure that the CPU is either switched off or in STOP mode.
3. Insert the SIMATIC memory card, as shown on the CPU, into the slot for the SIMATIC
memory card.
4. Carefully insert the SIMATIC memory card into the CPU, pushing gently, until the card
clicks into place.
5. Insert the other SIMATIC memory card into the right-hand CPU as described in steps 1 to
4The SIMATIC R/H redundant system has been installed. The system has been
wired. The SIMATIC memory cards are in the CPUs. The load current supply is connected to
the power supply.
Procedure:
Turn on the load current supply.
Result:
● The CPUs run a flash test and on completion of system initialization goes to STOP. The
RUN/STOP LEDs on both CPUs are yellow.
● The two CPUs implement pairing. The ERROR LEDs are flashing red. In STEP 7 in the
diagnostic status (Online & diagnostics) of the R/H system, check successful
paring. "Paired" is shown in the "Pairing state" field.Redundant operation is only possible if the two CPUs have different redundancy IDs. The
redundancy IDs can have values of 1 and 2. Both CPUs have redundancy ID 1 in the
configuration as the default:
The redundancy ID is used to assign a project tree to the real CPU in STEP 7. The upper
CPU of the two in the tree always has a redundancy ID of 1. The lower CPU of the two
always has the redundancy ID 2.
Requirements:
Both CPUs are in STOP. There is pairing between the two CPUs.
Procedure:
1. On the CPU display of the right CPU, select the menu item "Overview> Redundancy".
2. Assign the CPU redundancy ID 2.
Result: The right-hand CPU in the configuration is assigned redundancy ID 2.In the example, download the project data from the PG/PC to the primary CPU via an online
connection. The project data (all configuration data and the complete user program) can only
be downloaded when a CPU is in STOP operating state.
Procedure:
1. Right-click to select the R/H system in the project tree.
2. Select the "Download to device" > "Hardware and software (changes only)" command
from the shortcut menu.
Result: The "Extended download" dialog window opens.
3. Select the PG/PC interface.
4. Select the interface to which the PG/PC is connected.