The basic submodule is not yet configured.The figure below shows the assignment of the address |
|
pace for submodules 1 and 2Address space for configuration as 1 x 16-channel DQ |
|
16x24VDC/0.5A BA MSO with |
|
value statusThe figure below shows the assignment of the address space with submodules 3 and 4The module has no selectable diagnostics. Diagnostics alarms, for example, cannot be
output with STEP 7 (TIA Portal).
5.1 Status and error displays
LED displays
The figure below shows you the LED displays (status and error displays) of the
DQ 16x24VDC/0.5A BA.The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1 RUN/ERROR status and error displays
LED Meaning Remedy
RUN ERROR
Off Off
Voltage missing or too low at backplane bus. • Switch on the CPU and/or the system power
supply modules.
• Verify that the U connectors are inserted.
• Check to see if too many modules are inserted.
Flashes Off
Module is starting up. ---
On Off
Module is ready.
Flashes Flashes
Hardware defective. Replace the module.
LED PWR1/PWR2
Table 5- 2 PWR1/PWR2 status display
LED PWRx Meaning Remedy
Off
Supply voltage L+ too low or missing. Check the L+ supply voltage.
On
Supply voltage L+ is present and OK. ---
LED CHx
Table 5- 3 CHx status display
LED CHx Meaning Remedy
Off
0 = Status of the output signal. ---
On
1 = Status of the output signal.Hardware version E01
Firmware version V1.0.0
Product function
I&M data Yes
Engineering with
STEP 7 TIA Portal can be configured/integrated
as of version
V13 / V13
STEP 7 can be configured/integrated as of version V5.5 SP3 / -
Operating mode
MSO Yes
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
Permitted range, low limit (DC) 20.4 V
Permitted range, high limit (DC) 28.8 V
Reverse polarity protection Yes; with internal protection with 7 A per group
Input current
Current consumption, max. 30 mA
Power
Power taken from the backplane bus 1.15 W
Power loss
Power loss, typ. 2.2 W
Digital outputs
Type of digital output Transistor
Number of outputs 16
Sourcing output Yes
Digital outputs, configurable No
Short-circuit protection Yes
• Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-53 V)
Activation of a digital input Yes With resistive load, max. 0.5 A
With lamp load, max. 5 W
Load resistance range
Low limit 48 Ω
High limit 12 kΩ
Output voltage
Type of output voltage DC
for signal "1", min. L+ (-0.8 V)
Output current
For signal "1" rated value 0.5 A
For signal "1" permitted range, max. 0.5 A
For signal "0" residual current, max. 0.5 mA
Output delay with resistive load
"0" to "1", max. 100 µs
"1" to "0", max. 500 µs
Parallel switching of 2 outputs
For logical operations Yes
For increased performance No
For redundant activation of a load Yes
Switching frequency
With resistive load, max. 100 Hz
With inductive load, max. 0.5 Hz; acc. to IEC 947-5-1, DC13
With lamp load, max. 10 Hz
Total current of the outputs
Max. current per channel 0.5 A; see additional description in the manual
Max. current per group 4 A; see additional description in the manual
Max. current per module 8 A; see additional description in the manual
Cable length
Cable length shielded, max. 1000 m
Cable length unshielded, max. 600 m
Interrupts/diagnostics/status information
Substitute values can be applied No
Interrupts
Diagnostics interrupt No
Diagnostics alarms
Diagnostics No
Diagnostics indicator LED
RUN LED Yes; green LED
ERROR LED Yes; red LED
MAINT LED No
Monitoring of the supply voltage Yes; green LED
Channel status display Yes; green LEDBetween the channels No
Between the channels, in groups of 8
Between the channels and the backplane bus Yes
Permitted potential difference
Between different circuits 75 VDC / 60 VAC (basic isolation)
Isolation
Isolation tested with 707 VDC (type test)
Distributed mode
Prioritized startup Yes
Dimensions
Width 25 mm
Height 147 mm
Depth 129 mm