Home ProductsTAMAGAWA

TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63

TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63

    • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63
    • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63
    • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63
    • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63
    • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63
  • TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63

    Product Details:

    Place of Origin: Japan
    Brand Name: Tamagawa
    Certification: CE
    Model Number: TS5016N63

    Payment & Shipping Terms:

    Minimum Order Quantity: 1pcs
    Packaging Details: carton
    Delivery Time: in stock
    Payment Terms: T/T, Western Union, MoneyGram
    Supply Ability: 100pcs/week
    Contact Now
    Detailed Product Description
    Tamagawa: Tamagawa TS5016N63: TS5016N63
    Japan: Japan Material: Iron
    Color: Black Temperature: 30-80
    WIRE: Wire

     

     TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63TAMAGAWA TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63 TS5016N63

    assignment (= and /=) boxes where you specify a bit You can specify an immediate write of a physical output
    using ":P" following the Q offset (example: "%Q3.4:P").
    address for the box output. Box inputs and outputs can be For an immediate write, the bit data values are written to
    the process image output and directly to physical output.
    connected to other box logic or you can enter a bit
    address.
    output coil or an FBD "=" box is enabled, then the output

    Guang Zhou Lai Jie Electric Co.,LTD

    TS5016N63

    TS3630N3E6

    TS3630N1303E9

    TS3630N1306

    TS3630N11E1

    TS3630N11E2

    TS3630N12E3

    TS3630N12E4

    TS3630N13E5

    TS3630N13E6

    FA-CODER

    TS5214N566

    TS5205N450

    TS5205N454

    TS5205

    N450

    TS5205

    N454

    TS5205N452

    TS5205

    N452

    TS5207

    TS5208

     

     

    If there is no power flow through an output coil or an FBD "=" assignment box is not
    enabled, then the output bit is set to 0.
    ● If there is power flow through an inverted output coil or an FBD "/=" box is enabled, then
    the output bit is set to 0.
    ● If there is no power flow through an inverted output coil or an FBD "/=" box is not enabled,
    then the output bit is set to 1. When S (Set) is activated, then the data value at the OUT
    address is set to 1. When S is not activated, OUT is not
    changed.
    Not available When R (Reset) is activated, then the data value at the OUT
    address is set to 0. When R is not activated, OUT is not
    changed. IN (or connect to contact/gate logic) Bool Bit location to be monitored
    OUT Bool Bit location to be set or reset When SET_BF is activated, a data value of 1 is assigned to "n"
    bits starting at address OUT. When SET_BF is not activated,
    OUT is not changed.
    Not available RESET_BF writes a data value of 0 to "n" bits starting at
    address OUT. When RESET_BF is not activated, OUT is not
    changed. Starting element of a bit field to be set or reset (Example:
    #MyArray[3])
    n Constant (UInt) Number of bits to write RS is a set dominant latch where the set dominates. If the set (S1) and reset (R)
    signals are both true, the output address OUT will be 1.
    Not available SR is a reset dominant latch where the reset dominates. If the set (S) and reset
    (R1) signals are both true, the output address OUT will be 0. The OUT parameter specifies the bit address that is set or reset. The optional OUT output Q
    reflects the signal state of the "OUT" address. LAD: The state of this contact is TRUE when a positive transition (OFFto-ON)
    is detected on the assigned "IN" bit. The contact logic state is
    then combined with the power flow in state to set the power flow out
    state. The P contact can be located anywhere in the network except the
    end of a branch.
    FBD: The output logic state is TRUE when a positive transition (OFFto-ON)
    is detected on the assigned input bit. The P box can only be
    located at the beginning of a branch.
    Not available LAD: The state of this contact is TRUE when a negative transition (ONto-OFF)
    is detected on the assigned input bit. The contact logic state is
    then combined with the power flow in state to set the power flow out
    state. The N contact can be located anywhere in the network except
    the end of a branch.
    FBD: The output logic state is TRUE when a negative transition (ON-toOFF)
    is detected on the assigned input bit. The N box can only be
    located at the beginning of a branch. LAD: The assigned bit "OUT" is TRUE when a positive transition (OFFto-ON)
    is detected on the power flow entering the coil. The power flow
    in state always passes through the coil as the power flow out state. The
    P coil can be located anywhere in the network.
    FBD: The assigned bit "OUT" is TRUE when a positive transition (OFFto-ON)
    is detected on the logic state at the box input connection or on
    the input bit assignment if the box is located at the start of a branch.
    The input logic state always passes through the box as the output logic
    state. The P= box can be located anywhere in the branch.
    Not available LAD: The assigned bit "OUT" is TRUE when a negative transition (ONto-OFF)
    is detected on the power flow entering the coil. The power flow
    in state always passes through the coil as the power flow out state. The
    N coil can be located anywhere in the network.
    FBD: The assigned bit "OUT" is TRUE when a negative transition (ONto-OFF)
    is detected on the logic state at the box input connection or on
    the input bit assignment if the box is located at the start of a branch.
    The input logic state always passes through the box as the output logic
    state. The N= box can be located anywhere in the branch. The Q output power flow or logic state is TRUE when a positive transition
    (OFF-to-ON) is detected on the CLK input state (FBD) or CLK power flow
    in (LAD).
    In LAD, the P_TRIG instruction cannot be located at the beginning or end
    of a network. In FBD, the P_TRIG instruction can be located anywhere
    except the end of a branch.
    Not available The Q output power flow or logic state is TRUE when a negative transition
    (ON-to-OFF) is detected on the CLK input state (FBD) or CLK power flow
    in (LAD).
    In LAD, the N_TRIG instruction cannot be located at the beginning or end
    of a network. In FBD, the N_TRIG instruction can be located anywhere
    except the end of a branch. Memory bit in which the previous state of the input is saved
    IN Bool Input bit whose transition edge is to be detected
    OUT Bool Output bit which indicates a transition edge was detected
    CLK Bool Power flow or input bit whose transition edge is to be detected
    Q Bool Output which indicates an edge was detected All edge instructions use a memory bit (M_BIT) to store the previous state of the input signal
    being monitored. An edge is detected by comparing the state of the input with the state of
    the memory bit. If the states indicate a change of the input in the direction of interest, then an
    edge is reported by writing the output TRUE. Otherwise, the output is written FALSE.
    Note
    Edge instructions evaluate the input and memory-bit values each time they are executed,
    including the first execution. You must account for the initial states of the input and memory
    bit in your program design either to allow or to avoid edge detection on the first scan.
    Because the memory bit must be maintained from one execution to the next, you should use
    a unique bit for each edge instruction, and you should not use this bit any other place in your
    program. You should also avoid temporary memory and memory that can be affected by
    other system functions, such as an I/O update. Use only M, global DB, or Static memory (in
    an instance DB) for M_BIT memory assignments.
    7.2 Timers
    You use the timer instructions to create programmed time delays. The number of timers that
    you can use in your user program is limited only by the amount of memory in the CPU. Each
    timer uses a 16 byte IEC_Timer data type DB structure to store timer data that is specified at
    the top of the box or coil instruction. STEP 7 automatically creates the DB when you insert
    the instruction.The TONR timer sets output Q to ON after a
    preset time delay. Elapsed time is accumulated

    Contact Details
    Guang Zhou Lai Jie Electric Co.,Ltd

    Contact Person: Mr. Tommy

    Tel: 86-020-87268766

    Fax: 86-020-87269099

    Send your inquiry directly to us (0 / 3000)